WI-I/O 9-L Configuration Manual

WI-I/O 9-L Wireless I/O

page 70 of 108

Unit sensitivities indicate the change required in an analog input for the WI-I/O 9-L-T to detect

a state change and trigger any mapping that includes the input.
If you set the sensitivity to a small value, the mappings using the input will trigger on a small

change of value. If the input is noisy or variable, this can congest the radio channel by

sending multiple spurious messages. You can overcome this situation by increasing the

sensitivity value.
To set unit sensitivities:

1. Open the project.
2. Select the unit you want to change.
3. Select

Sensitivities

4. WI Series shows the sensitivities for the unit:

5. Select the sensitivity you want to change and click

Edit Sensitivities

.

6. WI Series shows the sensitivity:

7. Set the sensitivity as required and click

OK

to set the new value or click

Cancel

to return to the sensitivity list without changing the sensitivity.

8. WI Series will write the new sensitivity value to the module when you reconfigure it.