Setting the fault action, Setting the fault action -9 – Rockwell Automation 1203-SSS Smart Self-powered Serial Converter User Manual

Page 25

Advertising
background image

Configuring the Serial Converter

3-9

By default, when DF1 serial communications are disrupted (e.g., a serial
cable is disconnected) and control I/O is being transmitted, the serial
converter and connected product respond by faulting. You can set the
following actions:

To change the fault action

• Set the value of Parameter 04 - [Comm Flt Action] to the desired

fault action.

Figure 3.8 Comm Flt Action Parameter in HyperTerminal

Changes to this parameter take effect immediately. A reset is not
required.

Setting the Fault Action

Action

Description

Fault

The product will fault.

Stop

The product will stop and not fault (DPI host products only).

Zero data

The product is sent 0 for output data after a communications disruption.
This does not command a stop.

Hold last

The product continues in its present state after a communications
disruption.

!

ATTENTION: Risk of injury or equipment damage exists.
Parameter 04 - [Comm Flt Action] lets you determine the action of
the serial converter and connected product if communications are
disrupted. By default, this parameter faults the product. You can set this
parameter so that the product continues to run. Precautions should be
taken to ensure that the setting of this parameter does not create a
hazard of injury or equipment damage.

Press the UP ARROW or DOWN ARROW key to scroll

through the parameter list. Press the LEFT ARROW or

RIGHT ARROW key to modify parameter values. Press

the ENTER key to save a new value.

4> Comm Flt Action = Fault