B-3

No.

Name and Description

Details

14

[NAK No Memory]

(1)

Number of NAKs sent by the serial converter because it
did not have sufficient memory to buffer the incoming
messages. The serial converter runs out of memory if a
command has not completed and there is no place to
save the new commands.

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

15

[Duplicate Msgs]

(1)

Number of duplicate messages sent by the serial
converter. This value contains the total number of
consecutive messages received by this device with the
same TNS (Transaction Sequence) number.

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

16

[Interface Select]
Auto

Converter will automatically run DPI if
connected to a DPI product or SCANport if
connected to a SCANport product.

SCANport

Converter will perform SCANport services
only.

Set this parameter to “Auto” (default) unless you are using
DriveExplorer v1.xx or DriveTools32 v2.xx software and
you are connected to a DPI product. Use “SCANport” for
these software versions.

Default:

0 = Auto

Values:

0 = Auto
1 = SCANport

Type:

Read/Write

17

[DPI Data Rate]

(2)

Data rate used by the DPI host product. This data rate is
set in the drive, and the adapter autobauds to it.

Default:

0

Values:

0 = 125 kbps
1 = 500 kbps

Type:

Read Only

18

[DF1 Addr Actual]

(2)

DF1 address actually used by the serial converter.

Default:

1

Minimum:

0

Maximum:

254

Type:

Read Only

19

[DF1 Rate Actual]

(2)

Serial port rate actually used for the DF1 serial port on the
serial converter.

Default:

0 = 9600

Values:

0 = 9600
1 = 19.2K
2 = 38.4K

Type:

Read Only

20

[Ref/Fdbk Size]

(2)

Size of the Reference/Feedback. The host product
determines the size of the Reference/Feedback. The
serial converter automatically uses the correct size.

Default:

0 = 16-bit

Value:

0 = 16-bit
1 = 32-bit

Type:

Read Only

21

[Datalink Size]

(2)

Size of each Datalink word. The host product determines
the size of Datalinks.

Default:

0 = 16-bit

Values:

0 = 16-bit
1 = 32-bit

Type:

Read Only

(1)

This value is normally a low value. If it is continually incrementing and you are having
communications problems, use a lower baud rate or replace the 1203-SFC serial cable.

(2)

The parameter appears only when the serial converter is connected to a product implementing
DPI.