Appendix b, Parameter list, Serial converter parameters – Rockwell Automation 1203-SSS Smart Self-powered Serial Converter User Manual

Page 37: Serial converter, Parameters, Bserial converter parameters, Appendix

Advertising
background image

Appendix

B

Serial Converter Parameters

This chapter presents information about the parameters in the serial
converter.

Parameter List

No.

Name and Description

Details

01

[Adapter Port]
Port on the host product to which the serial converter is
connected.

Default:

0

Minimum:

0

Maximum:

7

Type:

Read Only

02

[DF1 Addr Cfg]
DF1 node address for the serial converter. This is a
decimal value.

Default:

1

Minimum:

0

Maximum:

254

Type:

Read/Write

Reset Required: Yes

03

[DF1 Rate Cfg]
Serial port rate for the DF1 serial port on the serial
converter.

Default:

0 = 9600

Values:

0 = 9600
1 = 19.2K
2 = 38.4K

Type:

Read/Write

Reset Required: Yes

04

[Comm Flt Action]
Action that the serial converter and product take if the
serial converter detects that DF1 serial
communications are disrupted. This setting is effective
only if control I/O is transmitted through the serial
converter.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop (DPI) or
Fault (SCANport)
2 = Zero Data
3 = Hold Last

Type:

Read/Write

Reset Required: No

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 04 -
[Comm Flt Action]
lets you determine the action of the serial converter and
connected product if communications are disrupted. By default, this
parameter faults the product. You can set this parameter so that the product
continues to run. Precautions should be taken to ensure that the setting of
this parameter does not create a hazard of injury or equipment damage.