B-2

Serial Converter Parameters

No.

Name and Description

Details

05

[Reset Module]
Ready

No action.

Reset Module

Resets the serial converter.

Set Defaults

Restores the serial converter to its
factory-default settings.

This parameter is a command. It will be set to “Ready”
after a “Reset Module” command or “Set Defaults”
command has been performed.

Default:

0 = Ready

Values:

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

06

[Clear DF1 Counts]
No action if set to “Ready.” Resets the DF1 statistical
parameters (numbers 07 – 15) to 0 if set to “Clear
Counts.” This parameter is a command. It will be reset to
“0 = Ready” after a “Clear Counts” command has been
performed.

Default:

0 = Ready

Values:

0 = Ready
1 = Clear Counts

Type:

Read/Write

07

[DF1 Packets Sent]
Number of DF1 packets sent by the serial converter. The
value of this parameter is normally approximately equal to
the value of Parameter 08 - [DF1 Packets Rcvd].

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read Only

08

[DF1 Packets Rcvd]
Number of DF1 packets received by the serial converter.
The value of this parameter is normally approximately
equal to the value of Parameter 07 - [DF1 Packets Sent].

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read Only

09

[Undelivered Msgs]

(1)

Number of DF1 messages that were sent but not
acknowledged.

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

10

[ENQs Sent]

(1)

Number of ENQ characters sent by the serial converter.

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

11

[ENQs Received]

(1)

Number of ENQ characters received by the serial
converter.

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

12

[NAKs Received]

(1)

Number of NAK characters received by the serial
converter.

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

13

[NAK Bad Packet]

(1)

Number of NAKs sent by the serial converter because of
corrupt packets (improper protocol messages) as
determined by the serial converter.

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

(1)

This value is normally a low value. If it is continually incrementing and you are having
communications problems, use a lower baud rate or replace the 1203-SFC serial cable.

!

ATTENTION: Risk of injury or equipment damage exists. If the serial
converter is transmitting control I/O to the product (indicated by a
solid green diamond LED), the product may fault when you remove
or reset the serial converter. Determine how your product will
respond before removing or resetting a connected serial converter.