Rockwell Automation 1203-SSS Smart Self-powered Serial Converter User Manual

Page 43

Advertising
background image

Flash Updates

C-3

2. If the Flash can be completed safely, type Y. The letter “C”

repeatedly appears. It is the Xmodem prompt and continues to
appear until you send a binary file.

Important: Press Ctrl + X to cancel a Flash update procedure.

3. Select Transfer > Send File to display the send file dialog box.

4. Click Browse and navigate to the Flash file.

5. Double-click the file. Its name appears in the Filename box.

6. In the Protocol box, select Xmodem.

Figure 4.6 Example Send File Dialog Box

7. Click Send. A dialog box appears and reports the progress of the

download. When it is complete, the message “Operation Complete”
appears.

Important: Keep the device powered for 15 seconds after the operation

has completed.

8. Press the Enter key to return to the main menu.