DIR 1000587R0002 (L3821)

(17)

L

(t=k/I

2

)

 

0.4xIn

≤ I

1

≤ 1xIn

3s ≤ t

1

≤ 144s

(1)

, step 3s

Release between

± 10%, I

f

6 In

curves IEC60255-3

step 0.01xIn

t1@ 3I

1

1.05 and 1.2xI1

± 20%, I

f

> 6 In

S

1

   

0.6 xIn ≤ I

2

≤10xIn

Min, 0.05s ≤ t

2

≤ 0.8s, step 0.01s

± 7%,I

g

≤ 6 In

The best of the two data

(t=k)

step 0.1xIn

0.10s ≤ t

2start-up

≤ 30s, step 0.01s

± 10%,I

g

> 6 In

± 10% or 40 ms

0.6 xIn ≤ I

2 start-up

≤10xIn

0.04s ≤ t

2sel

≤ 0.20s, step 0.01s

step 0.1xIn

S

1

  

0.6xIn

≤ I

2

≤10xIn

0.05s ≤ t

2

≤ 0.8s,

± 7%,I

g

≤ 6 In

± 15%, I

g

6 In

(t=k/I

2

)

step 0.1xIn

step 0.01 at 10xIn

± 10%,I

g

> 6 In

± 20%, I

g

>

6 In

I

   

1.5xIn ≤ I

3

≤ 15xIn

≤ 30 ms

± 10%

(t=k)

step 0.1xIn

G

(3)

   

0.20xIn ≤ I

4

≤1xIn

0.1s ≤ t

4

≤ 1s, step 0.05s

The best of the two data

(t=k)

step 0.02xIn

0.1s ≤ t

4 start-up

≤ 1s, step 0.02s

± 7%

± 10% or 40 ms

0.04s ≤ t

4sel

≤ 0.2s, step 0.01s

when I>I4

G

(3)

   

0.20xIn ≤ I

4

≤1xIn

0.1s ≤ t

4

≤ 1s, step 0.05s

± 7% ± 15%

(t=k/I

2

)

step 0.02xIn

@I

g

>4In

U

   

2% ≤ I

6

≤ 90%

0.5s ≤ t

6

≤ 60s, step 0.5s

± 10%

The best of the two data

(t=k)

step 1%

± 10% or 40 ms

OT

   

Fixed, defined

Instantaneous

± 5°C _____

(temp=k)

by AB

Iinst

   

Automatic, defined

Instantaneous

by AB

MM

   

1.5xIn ≤ I

5

≤ 4xIn

≤ 30 ms

± 10%

(t=k)

step 0.1xIn

Load control

   

50%÷100% step 0.05xI

1

LC1/LC2

Warning Iw

   

0,3÷10I

n

step 0,05xI

n

± 10%

10÷40 ms

3.1.9.9

Summary table of the protection function settings for the LSIG-MM

Protection

Threshold

range

Time Tolerance

(2)

Time

range

Threshold

tolerance

(2)

Disabling

Disabling

TRIP only

Start-up threshold

Thermal memory

(1)

The minimum value of this trip is 1s regardless of the type of curve set (self-

protection)

(2)

These tolerances apply under the following conditions:

- self-powered relay at full power (without start-up)

- presence of auxiliary power supply

- two-phase or three-phase power supply

- preset trip time ≥ 100ms

(3)

Protection G is disabled for current values greater than 4In, where I4 < 0.4

In, greater than 6 In, where 0.5 In ≤ I4 < 0.8 In and greater than 8 In where I4

≥ 0.8 In.

For all cases not covered by the above assumptions, the following tolerance

values apply

Protections

Trip threshold

Trip time

L

Release between 1.05 and 1.25 x I1 ± 20%

S

± 10%

± 20%

I

± 15%

≤ 60ms

G

± 10%

± 20%

Others

± 20%

3.1.9.10

Table of measurements

Type of measurement

Tolerance

Range

%

Phase and neutral currents

0.3 ... 6 In

1.5

Internal ground fault current

0.3 ... 4 In

1.5

(internal source ground return)

Peak factor

0.3 ... 6 In

1.5