5.1.2.1 Data Logger enabling
The Data Logger can be enabled by entering a password:

5.1.2.2 Setting the sampling frequency

The menu enables setting frequency by which measurements are saved, among 4 fixed frequencies: 600 Hz, 1200 Hz, 2400 Hz or 4800 Hz.

Maximum duration of stored data recording (also see par. 5.1.3) depends on the frequency selected, and is given in the following table:

Frequency

RECoRDING TIME

600 Hz

27.3 s

1200 Hz

13.6 s

2400 Hz

6.8 s

4800 Hz

3.4 s

Note: Selection of sampling frequency is an important factor. As a matter of fact, presence of high-order harmonic waves may give rise to aliasing on processing of

collected data. Maximum frequency should be used in case of harmonic distortion, or else data processing may give results that do not match actual system conditions.

5.1.2.3

Setting the standard triggers

It is possible to select one of the following triggers.

1. None
2. Every alarm
3. L timing
4. Every trip

4/9

Data logger

Modules

Data logger

Main Frequency

Settings

1/6

On

Sampling freq.

Stop event

Enable

Data logger

1/4

600 Hz

1200 Hz

2400 Hz

600 Hz

Sampling freq.

Enter ↵

1/1

Off

Toroid size

Enable

Data logger

Password

Enter password

0***

2/2

Off

On

Off

Enable

Enter ↵

PWD + Enter ↵

3/4

None

Sampling freq.

Stop event

Enable

Data logger

1/5

None

Any Alarm

L Prealarm

None

Stop event

Any Trip

Custom

Enter ↵

5 Appendices

5.1 Data Logger (recorder)

The Data Logger function is available on the LSIG-MM units and can be used to automatically save the instantaneous values of certain analog

and digital measurements in a large-sized memory buffer by means of a Modbus bus, and transferred to any personal computer for processing.

The function stops recording every time a trip occurs in order to facilitate failure analysis.

5.1.1 General characteristics
Number of analog channels:

7

Number of digital events:

64

Maximum sampling frequency:

4800 Hz

Maximum sampling time:

27 s ( - 600 Hz sampling frequency)

5.1.2

Description of the Data Logger menu

From the Settings Menu of LSIG-MM units, access is given to Data Logger’s surfing menu: