DIR 1000587R0002 (L3821)

(28)

Failure to comply with the setting limits for “I

n

” and “I

n

N” can cause damage to circuit breaker with consequent risks even

for operator.

In any case, the relay records any setting error between

I

1

and Neutral setting, and it signals this by means of a warning (see par. 3.5.2).

For

4-pole CBs only.

3.4.4.3

Mains frequency settings

In the Mains frequency menu, frequency values: 50, 60 Hz can be selected.

2/9

50 Hz

Main Frequency

Modules

Circuit Breaker

Settings

Password

Enter password

0***

1/2

4 P

60 Hz

50 Hz

Main Frequency

Enter ↵

Enter ↵

3.4.4.4 Modules

3.4.4.4.1 Communication module

Local or remote modes can be set after entering a password. The serial address can be displayed after entering a password. Baud Rate can be

set to 9600 and 19200 bit/s. The physical protocol provides for options: (8,E,1), (8,O,1), (8,N,2), (8,N,1). For further information on the communi-

cation module, see paragraph 4.2 in this manual.

3.4.5 Test Menu
Access to the Test menu is password-protected.

The menu shows the state of the CB; the dialog module (COM module), the state of the springs and the position of the CB; and in this submenu

you can have the CB opened or closed.

Using the “Trip Test” function, Trip disabling/enabling can be viewed. When enabled, the circuit breaker is opened. This function is only available

with a nil busbar current (use Vaux or battery unit).

On the page, only with Vaux, you can also see the state of “STATUS” circuit breaker, thus making sure that input is correctly wired.

The surfing path is summarized in the following table:

3.4.5.1

Test Menu table

Parameter/Function

Values

Notes

CB status

Open/Closed/Indefinite

Indefinite only in the event of a fault

Auto Test

Display test

Trip Test

Enabled/Disabled

Communication State of springs

Unloaded/Loaded

module

Position of CB

Isolated/Withdrawn

Open CB

Close CB

MM Test

Autotest

2/4

Parametri di comunicazione

Module

COM

Moduli

1/5

Locale

Indirizzo Seriale
BaudRate

Local / Remote

Modulo COM

4/5

Device test

Settings

Test

Measures

Menu

Password

Enter password

0***

1/6

CB open

Auto Test

Trip Test (disabled)

CB status

Test

Enter ↵

Enter ↵