The configuration parameters in the Settings menu are password-protected. Among the most

significant values that can be selected, note the neutral threshold (values 50%, 100%, 150%,

200%), mains frequency of installation (values 50 Hz, 60 Hz). For a more detailed description of

the settings for the modules, refer to the documentation on the modules (ch. 4).

1/5

Protections settings

Measurements

Settings

Protections

Menu

1/9

Circuit breaker settings

Main Frequency

Modules

Circuit Breaker

Settings

1/3

Neutral settings

Neutral Protection

Unit installation

Ground protection

Circuit Breaker

On

Neutral threshold

Enable

Neutral protection

2

1/2

Enter ↵

Enter ↵

Enter ↵ + PWD

3.4.4.1

Settings Menu table

Parameter/Function

Values

Notes

Circuit

(*) Neutral protection

breaker

Enable

ON/OFF

Neutral threshold

50%-100%-150%-200%

Mains frequency

50 Hz - 60 Hz

Modules

Module

Communication module

if installed

see par. 3.4.4.4.2

Local Bus unit

Installed-Not installed

(*) With the three-pole circuit breaker, the “3P+N” option is displayed and must be enabled if the outside neutral is installed.

Parameter/Function

Values

Notes

Data Logger Enable

ON/OFF

See Annex par. 5.1

Sampling frequency

Trigger

Stopping delay

Restart

Stop

Measurement interval

from 5 to 120 min, step 5 min

Harmonic distortion

ON/OFF

The warning indicates that the distortion exceeds

factor 2.1

System

Date

Time

Language

English/Italiano/Français/Deutsch/Español

New password

Display

Contrast

3.4.4.2

Adjusting the neutral

Neutral protection is normally set to a current value 50% of the adjustment made on the phases.

In some installations, where particularly high harmonics occur, the current running on neutral may be higher than that of phases.

In the LSIG-MM releases, this protection can be set for the following values: I

n

N = 50% - 100% - 150% - 200% * I

n

.

The values that can be used to adjust the neutral are given in the table below for the various possible combinations between types of circuit-

breaker and adjustment of threshold I

n

.

Neutral value (InN) adjustment will meet the following formula: I

1

x I

n

N

≤Iu

When a 4-pole CB is available, this setting is controlled by the relay which signals the fault through a LED (see par. 3.5.1) , and automatically

adjusts the parameter, within the accepted limits.

When a 3-pole CB with external neutral is available, the relay does not perform any control and settings are to be adjusted by user.

E.g.:

With 140G-N 1200 with Rating Plug at 400A, Iu=1200A and I1=1In, adjustment of I

n

N may be 50-100-200%

With 140G-N 1200 with Rating Plug at 800A, Iu=1200A and I1=1In, adjustment of I

n

N may be 50-100%


Note 1: I

1

=1I

n

setting is intended as maximum adjustment of protection against overloads. Actual maximum allowable adjustment must take into account any temperature

derating, terminals used and altitude, or In (rating plug)

≤ 50% of circuit breaker size.