Rockwell Automation 140G-NTK-E12 LSIG and LSIG-MM Release User Manual

Page 31

Advertising
background image

DIR 1000587R0002 (L3821)

(31)

3.6 Troubleshooting LSIG-MM units

The following table lists a series of typical service conditions, to help you understand and solve hypothetical faults or malfunctions.

N.B.:

1. Before consulting the following table, check for any error messages appearing for some seconds on the display.

2. FN indicates normal operation of the release.

3. When the suggestions proposed do not lead to a solution of the problem, please contact ABB SACE assistance service.

No.

Situation

Possible causes

Suggestions

1

Trip test cannot be run

1. Busbar current is > 0

1. FN

2. The TC is not connected

2. Check messages on the display

2

Trip times lower

1. Threshold too low

1. Correct threshold

than expected

2. Curve too low

2. Correct curve

3. Thermal memory enabled

3. Exclude if not necessary

4. Incorrect neutral selection

4. Correct Neutral selection

3

Trip times higher

1. Threshold too high

1. Correct threshold

than expected

2. Curve too high

2. Correct curve

3. Curve I

2

t enabled

3. Exclude if not necessary

4. Incorrect neutral selection

4. Correct Neutral selection

4

Rapid trip, with I3=Off

Iinst tripped

FN short-circuit with high I

5

High earth fault current value,

1. Incorrect selection of sensor

1. Set int. or ext. sensor

but no trip takes place

2. Function G prevented with I>4 In

2. FN

6

Display off

1 No Vaux and current and/or

1. FN, see 3.1.2.1

voltage is below the minimum value.

2. Temperature off-range

2. FN, see 3.1.9.6

7

The display is not back-lit

Current and/or voltages below the

FN

limit for lighting the display

8

Reading of I incorrect

Current below the minimum

FN

threshold that can be displayed

9

Message “”

Function disabled or data off-range

FN

instead of expected data

10

Expected trip does not take place

Trip function disabled

FN enable trip if necessary

11

No activation of protection

Values of I out of range

FN, see 3.1.9.3

Unbalance U

12

No display of

No Vaux , buffer capacitor

FN, see 3.4.6.1

opening data

is discharged

13

The password is not requested

The password has been disabled

FN, re-enter the password with a value

other than 0000

14

Impossible to change any

Release in an alarm situation

FN

parameter

15

Message “ Temp. Sensor” or

Possible fault inside the relay

Contact AB

“ Start-up”

18

Invalid Date

1. First installation

FN see 3.3.3.

2. Information lost due to power

failure

19

Untimely trip

see 3.5.2

20

LED lighting

see 3.5.1

21

No possibility to change

1. Relay is remotely set

1. Set to local

language

2. The CB is not open

2. Open CB

3. Vaux or battery unit

3. Power the relay