Rockwell Automation 140G-NTK-E12 LSIG and LSIG-MM Release User Manual

Page 41

Advertising
background image

DIR 1000587R002 (L3821)

Pubblication 140G-IN067A-MU-P - April 2013

5.1.4 Data Logger commands from system

As a consequence of a Stop Data Logger command, storage will be stopped from system. Any subsequent recording is enabled following a

Restart trigger command. The same operations can be performed from the operator panel as given in par. 5.1.2.6.

Example of Data Logger operation

The following figure shows an example of how trigger and Data Logger operate, and influence of stopping delay and restart and subsequent

stoppage of the data storage phase.

Samples

Samples
available

Samples
available

Trigger

Waiting Trigger

Modbus commands

Datalogger Triggered

Datalogger Stopped

Stopping

delay

Data logger enabled

5.2 Event list table

5.2.1 “Standard” events for the Data Logger function, selectable from the relay

Event no.

Description

0.

None

(free running)

1.

Any alarm

2.

L timing

(L protection timing)

3.

Any trip

(tripping of any protection)

5.2.2 Examples of “custom” events for Data Logger function

No. (decimal)

Event

Notes

LSIG-MM

1920

G timing

x

2894

L1 or L2 or L3 sensor error or Trip Coil error

x

2688

LC1 alarm

x

2049

G alarm

x

33672

CB connected and spring loaded

x

1793

Harmonic distortion > 2.1

x

You can combine the status bits with “and” / “or” logical functions within the same group of events (byte). For more detailed information, refer to

the Modbus Interface document.

5.2.3 Combining the devices needed to customize settings

“Custom” events can be selected using a remote control system.

The devices needed to do so can be selected from among the following:

LSIG-MM + Dialog unit