Rockwell Automation 140G-NTK-E12 LSIG and LSIG-MM Release User Manual

Page 23

Advertising
background image

DIR 1000587R0002 (L3821)

(23)

3.3.4 Default settings
The LSIG-MM are supplied by AB with the following predefined parameters (Set A and Set B):

#

Protection

On/Off

Thresholds

Time

Curve

T.M.

Trip

1

L

1 In

144 s

I

2

t

Off

2

S

Off

6 In

50 ms

K

3

I

On

4 In

4

G

Off

0.2 In

0.4 s

K

On

5

U

Off

50 %

5 s

Off

6

OT

Off

7

Language

Engl

8

Mains frequency

(1)

9

Sel. Neutral

(2)

10

S startup

Off

6 In

100 ms

11

G startup

Off

1 In

100 ms

12

Password

0001

13

Measurement interval

60 min

14

Iw

Off

3 In

15

MM

On

2.5 In

Note:

(1)

= 50Hz for automatic Circuit-Breakers IEC

60Hz for automatic Circuit-Breakers UL

(2)

= off for 3-pole version

50% for 4-pole version