Rockwell Automation 140G-NTK-E12 LSIG and LSIG-MM Release User Manual

Page 37

Advertising
background image

DIR 1000587R0002 (L3821)

(37)

4.2.6 Communication Module Menu

Parameter/Function

Values

Notes

Local/Remote

Local/Remote

Serial address

1 ... 247

247 default address

Baudrate

9600 bit/s

19200 bit/s

Physical protocol

8,E,1 - 8,0,1 - 8,N,2 - 8,N,1

Addressing

standard Modbus

4.3 Contact S51/MM

4.3.1 General characteristics

The contact gives feedback about "MM" protection enabled.

4.3.2 Characteristics of the signalling contacts

The following data are defined for resistive loads (cos ϕ = 1)

4.3.3 Power supply
The S51/MM signalling contact is self-powered, by auxiliary power from the relay.

Type of contact

SPST

Maximum switching voltage

130 Vdc 380 Vac

Maximum switching current

5 A

8 A

Maximum switching power

175 W

2000 VA

Breaking capacity @ 35 Vdc

5 A

——

Breaking capacity @ 120 Vdc

0.2 A

——

Breaking capacity @ 250 Vac

——

8 A

Breaking capacity @ 380 Vac

——

5.2 A

Contact/coil insulation

4000 V eff

Contact/contact insulation

1000 V eff

Advertising
This manual is related to the following products: