Wiring the connector, Wiring the connector -7 – Rockwell Automation 160PD1 160 Profibus Communication Module User Manual

Page 17

Advertising
background image

Installation and Wiring

3–7

Wiring the Connector

The examples below can be used as a guide when wiring.

Important: Keep communication wiring away from high noise sources

such as motor cables. Use terminated cable only for the
last node (end of chain)

Figure 3.6
Wiring the PD1 Connector

The PDP network cables are connected to the PD1 module using a
9-pole D-Shell connector with a suitable opening facing downwards.
The pin layout of the connector follows the Profibus standard.
The Vcc (pin 6) and GND signal (pin 5) can be used for external bus
termination.

Important: Only use cable that conforms to ProfiBus cable standards.

Belden type 3079A ProfiBus cable or equivalent is
recommended.

Figure 3.7
Cable Termination

Termination resistors are only required at both ends of the network

Pin

Name

Function

Case

Shield

Bus cable shield. Connected to PE internally on the PD1

3

B-Line

Positive

5

GND BUS

Isolated GND

6

+5V BUS

Isolated +5V Vcc*

8

A-Line

Negative

9-Pin, Female D-Shell Connector

Pin 1

Pin 9

Ground Connection
Terminal

3 RxD/TxD-P

Vcc 6

390 220 390 Ohm

A

B

RxD/TxD-P 3

RxD/TxD-N 8

GND 5

8 RxD/TxD-N

Advertising