Rockwell Automation 160PD1 160 Profibus Communication Module User Manual

Page 49

Advertising
background image

Troubleshooting

8–3

Table 8.B (continued)

160 Drive

1

Fault Codes

1

Refer to the 160 SSC™ Variable Speed Drive (Series C) User Manual for the most current fault code
information.

Table 8.C
Network Fault Codes

Fault Code Fault Indication

Description

Corrective Action

39

Phase V Fault

Phase to ground fault detected between drive
and motor phase V.

Check wiring between drive and motor.
Check motor for grounded phase.

40

Phase W Fault

Phase to ground fault detected between drive
and motor phase W.

Check wiring between drive and motor.
Check motor for grounded phase.

41

UV Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive
output terminals for a shorted condition.

42

UW Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive
output terminals for a shorted condition.

43

VW Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive
output terminals for a shorted condition.

48

Reprogramming Fault

Occurs when reset defaults is performed.

Clear fault.

49

Zero Overload Fault

Occurs when load requires excessive current at
zero hertz.

Reduce motor load and/or motor dwell time at zero
hertz.

Fault Code Fault Indication

Description

Corrective Action

51

Serial Fault

No serial Connection established

Check if SSC160 of version ‘C’ or higher has been
installed. (Refer to drives nameplate)
Check 30 pin connector on the options back.
Check parameter setting according to Section 5.

52

Network lost connection

Timeout on Network

Check connection between Master and Slave

53

False Drive Type

Drive Type is not compatible to option board

Check if SSC160 of version > ‘C’ has been installed.