Wiring the IB1 Ground Terminal

In addition to the ground connections shown in Appendix C of the
160 SSC manual, the ground terminal at the bottom of the IB1
module must be solidly connected (and as short as possible) to the
signal common terminal 3 at TB3 of the 160 SSC drive, as shown in
Figure 3.4:

This connection shall have a cross section of 1.5 mm

2

.

Figure 3.4
IB1 Module Grounding

R/L1

S/L2

T/L3

PE

AC

nput Line

Shielded Enclosure

Enclosure Ground Connection

U/T1

Shielded Motor Cable

to TB3

Control
Cabinet

to Motor

V/T2

W/T3

T (L3)

S (L2)

R (L1)

= EMC Tested Shielded Cable Clamp (or Metal Conduit)

When the control circuitry is located outside of the 160 enclosure.

Control Wiring TB3

Motor Wiring TB2

Ground Terminal – PE

Line Power TB1

Line

Filter

DC+

W/T3

1

3 4 5 6 7 8 9 10 11

2

V/T2

U/T1

DC–

BR+

T/L3

S/L2

R/L1

BR–

FAULT

READY

Ground Terminal – PE

IB1 Communication
Module

IB1 Ground Terminal