Troubleshooting

8–3

Drive faults can be read via index 0x603F. Refer to Table 8.C Table
8.D for fault number relation.

Drive fault codes can be read by accessing drive parameter P07 - [Last
Fault]
. Refer to Table 8.C and Table 8.D for fault descriptions/actions.

Table 8.C

160 Drive

1

Fault Codes

1

Refer to the 160 SSC™ V S D (Series C) User Manual for the most current fault code information.

7510

Serial interface to drive timeout

7520

Serial interface IBS bus not active

8100

Monitoring: Communication

36

8311

Monitoring/ Torque Control: Excess Torque

7

8313

Monitoring/ Torque Control: Standstill Torque

6

Fault No.
[Hex]

Fault Name

Fault Code
SSC160
[Dec]

Fault Code Fault Indication

Description

Corrective Action

00

No Fault

The drive is currently not faulted.

No action required.

03

Power Loss Fault

DC Bus voltage remains below 85% nominal on
power up for longer than 5 seconds.

Monitor incoming AC line for low voltage or line power
interruption.

04

Undervoltage Fault

DC Bus voltage fell below the minimum value while
the motor was running.

Monitor incoming AC line for low voltage or line power
interruption.

05

Overvoltage Fault

DC Bus maximum voltage exceeded.

Bus overvoltage caused by motor regeneration. Extend
the decel time, or install dynamic brake option or external
capacitor module.

06

Motor Stall Fault

Motor has stalled. Motor load is excessive.

Longer accel time or reduced load required.

07

Motor Overload Fault

Internal electronic overload trip. Excessive motor
load exists.

Reduce motor load.

08

Overtemperature Fault Excessive heat detected.

Clear blocked or dirty heat sink fins. Check ambient
temperature. Check for blocked or non-operating fan.

11

Operator Fault

The keypad has been removed while the drive is
powered.

Clear the fault. Do not remove the keypad underpower.

12

Overcurrent Fault

Overcurrent detected in hardware trip circuit.

Check short circuit at the drive output or excessive load
conditions at the motor.

13

Software Over
Current Fault

Motor current exceeded value set in parameter 79. A longer acceleration time, reduced load, or removal of

motor shaft blockage is required

20

Drive Overload Fault

An internal electronic overload trip has occurred.
The drive is overheating.

Clear blocked or dirty heat sink fins. Check ambient
temperature. Check for blocked or non-operating fan.

22

Drive Reset

Stop input not present.

Check stop input at TB3 terminal 8.

32

EPROM Fault

EPROM has invalid data.

Reset EPROM using P56 - [Reset Functions].

33

Max Retries Fault

Drive did not reset fault within the specified retries. Repair system fault.

36

Incompatible Fault

Incompatible communication module installed.

Verify compatibility of communication module.

38

Phase U Fault

Phase to ground fault detected between drive and
motor phase U.

Check wiring between drive and motor. Check motor for
grounded phase.

39

Phase V Fault

Phase to ground fault detected between drive and
motor phase V.

Check wiring between drive and motor. Check motor for
grounded phase.

40

Phase W Fault

Phase to ground fault detected between drive and
motor phase W.

Check wiring between drive and motor. Check motor for
grounded phase.

41

UV Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

42

UW Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

43

VW Short Fault

Excessive current has been detected between
these two drive output terminals.

Check the motor and external wiring to the drive output
terminals for a shorted condition.

46

Intermittent Phase
Fault

An external short occurred while running
diagnostics.

Check wiring between the drive and the motor. Check for
more than one shorted output.

48

Reprogramming Fault

Occurs when reset defaults is performed.

Clear fault.