Troubleshooting
IB1 Network Error Codes
The following error codes could be returned when accessing the IB1
Module.
Table 8.D
Network Fault Codes
Fault Code
Fault Indication
Description
Corrective Action
7510
Serial Fault
No serial Connection established
Check if SSC160 of version ‘C’ or higher has been
installed. (Refer to drives nameplate).
Check 30 pin connector on the options back.
Check Parameter setting according to Section 6.
7520
Unit lost Connection
Timeout on serial link
Check units plugs to SSC160 and IBS cable.
restart IBS master or drive
7500
Unit unrecoverable Fault
Unexpected Network Fault
5000
Model of Drive not valid
Use 160 Drive with version ’C’ or higher
Replace Drive