Using the 160-IB1 on InterBus

Create an InterBus Network
Configuration Frame

This example assumes that the SLC 500 rack has been configured
correctly with the SST-IBS-SLC card in slot 3. If configuration is
required an example of configuration is shown further in this chapter
– The InterBus PCP Telegram. Additionally it is assumed that a
160 drive with an 160-IB1 interface is connected on the InterBus
remote bus with a relevant 9 way D shell connector (see chapter 3).

Invoke Phoenix IBS CMD software and create a new project with
”File Menu” and ”New”.

Go to extended mode,.

then to the ”Settings” mode. On the ”Settings” dialogue box select the
Drivers tab and select the ”communication path” button.

In this example, the connection to the SST scanner is via a null
modem cable from the serial port on COM1 at 9600 baud.
Adjust the path accordingly and click OK twice.