Chapter

5

InterBus Parameter Descriptions
and Data Protocol

This chapter provides a listing and description of the Bulletin 160
Drive parameters related to Network Operation, and the IB1 Module
Data Protocol information.

Important: Refer to your 160 SSC™ Variable Speed Drive (Series C)

User Manual for drive parameter descriptions.

160 SSC Drive Parameters

Parameter Number

Access

[Parameter Name] and Description

Min./Max.
Values

Default

Drive

IB1

Index; Subindex

46

0x5FF0; 46
0x5FF9; 46

Read
Write

[Input Mode]
Configures the TB3 control inputs for various 3-wire or 2-wire control schemes.
Also enables/disables the program keypad module input control.
Settings: must be set to either

2 = Program Keypad Module control or
6 = 2-wire TB3 Control/Keypad or Communication control

A contact closure on TB3 terminals 7 and 8 is required for the drive to respond to a
Run command.
Important: This parameter cannot be programmed while the drive is running.

In addition, power must be cycled or P56 - [Reset Function] must be
set to 2 for the change to take effect.

0/9

0

59

0x5FF0; 59
0x5FF9; 59

Read
Write

[Frequency Select]
Selects the source of the frequency command for the drive.
The reference to P58 - [Internal Frequency] is bipolar, so a positive reference gives
forward rotation, and a negative reference gives reverse direction.
Settings:must be set to 1 = internal freq. command from P58 - [Internal Frequency].

0/1

0

66

0x5FF0; 66
0x5FF9; 66

Read
Write

[RPM Scaling]
A scaling factor is required to interpret a speed reference in RPM at the [Maximum
Frequency] of the drive. The 160 Drive parameter P66 - [Preset Frequency 5] is
used by the IB1 Module for this purpose.

P66 = rRPM / rf

rf:

required motor frequency to achieve rRPM

rRPM:

final RPM at application output (e.g. speed at gear box output),

which will be displayed at InterBus Master.

Application Speed [rpm] = Drive Output Frequency x P66 [RPM Scaling]
e.g.

1500 rpm = 50 Hz x 30

(4 pole motor)

P66 = 30.0 (300)

Gear Box 1:20:

75 rpm = 50 Hz x 1.5

(4 pole motor)

P66 = 1.5 (15)

For network operation the P66 values in brackets are valid, which are ten times the
values for keypad operation.

If P66 - [RPM Scaling] is set to 0, speed reference may be sent via the network
directly in 1/10 of Hz.
e.g. SpeedRef [Hz] (InterBus) = 405 results in 40.5 Hz of output frequency.

Speed feedback is considered to be P01 - [Output Frequency],
which reflects the output frequency considering ramp rates.

0-240
[0-2400]

50

Note:
P57 [Program lock] may be set to 1 (locked), but parameter programming via network will still be possible.

ATTENTION: Unpredictable motor speed can cause death,
injury or equipment damage. Do not use P66 as the [Preset
Frequency 5]
function via control terminal wiring.

!