Terminating resistors – Rockwell Automation 1500 DeviceNet MV Controllers Installation Instructions User Manual

Page 10

Advertising
background image

3-2

DeviceNet Cable System Layout for Medium Voltage Controller Structures

1500-IN057C-EN-P – June 2013

LV

LV

MV

MV

Female Linking Plug

Trunk Line

Drop Line

Drop Line Jumper

Male Linking Plug

Drop Line Jumper

LV

LV

MV

MV

Female Linking Plug

Trunk Line

Drop Line

Drop Line Jumper

Male Linking Plug

Drop Line Jumper

Figure 3.1 – Typical 2-High MV Section with DeviceNet Trunk and Drop Lines.

A T T E N T I O N

A T T E N T I O N

Before performing any service or maintenance

activities on MV MCC sections, disconnect all

power sources.

Terminating resistors are necessary at the ends of the trunk line to reduce

reflections of the communication signals on the network. The DeviceNet
network will operate correctly only when there are exactly two
terminating resistors, one at each end of the trunk line

. Terminating

resistors must be equal to 121 ohms 1%, 1/4W, metal film (terminating

resistor part number 1485A-C2).

MV controller line-ups ship with the terminating resistors installed at

opposite ends of the trunk line, located in the horizontal low voltage

wireway (on top of structure). A male plug connector with a terminating

resistor is connected at the right end of the trunk as shown in figure 3.2B.

A female plug connector with a terminating resistor is connected at the

left end of the trunk as shown in figure 3.2A. The resistors are inserted in

the second terminal from each end (connected to the white and blue

conductors) of both plugs (see diagram below).

Terminating Resistors