System Commissioning and Software Installation

7-3

1500-IN057

C-EN-P – June 2013


5. Use RSNetworx for DeviceNet to program and configure devices

(e.g., full load current, acceleration rate, etc.).

Do not download to a device before uploading from that device.

Otherwise, the node and baud rates will be overwritten, requiring

each device to be individually manually reprogrammed.

Make sure to set communication-loss behavior for each device.

I M P O R T A N T

I M P O R T A N T

RSNetworx for DeviceNet can also be used to change

baud rates and node numbers, but remember that the

devices are normally pre-programmed at the factory.

6. Use RSNetworx for DeviceNet to program the DeviceNet scanner (if

required).

I M P O R T A N T

I M P O R T A N T

When using a 2100-GK61 communication module,

keep in mind that there are two extra bytes of receive

data for the inputs on the 2100-GK61. Make sure the

number of bytes in the scanner configuration

corresponds with the number of bytes in the device.

See the 2100-GK61 user manual (publication 2100-

UM001_-EN-P, chapter 4) for more details.

7. Write the PLC program (if required).

8. If IntelliCENTER software is provided, load per the IntelliCENTER

Software User Guide (Publication 2100-UM002_-EN-P).