Chapter

8

1500-IN057C-EN-P – June 2013


Filling a Prepared Space in a MV Controller

Line-up with DeviceNet

General

Use this section when upgrading a Bulletin 1500 prepared space in a

DeviceNet MV controller with a controller kit. Each DeviceNet

component is factory wired within the controller kit and has a

communication cable that plugs into the device on one end and the other

end plugs into a DeviceNet port located on the flat vertical cable

assembly mounted on the left side of the low voltage panel. The

procedure varies depending on whether the controller kit is to fill the top

or bottom location of a 2-unit structure.

Note:

There is no need to re-evaluate the cumulative drop for this

network. The incremental increase in cumulative drop due to the

addition of the controller kit was taken into account when the MV

controller line-up was built.

Note:

When using IntelliCENTER software, new units must be added to

the software by installing the data disk(s) that accompanies the controller

kit. If an existing unit is moved, the user must update this change in the

IntelliCENTER software. Refer to IntelliCenter software manual,

pubication 2100-UM002_-EN-P.

Procedure for Top Unit

Note:

This procedure requires the bottom unit to be temporarily

disconnected from DeviceNet.

The prepared space does not have any DeviceNet connections. In order

to link the bottom unit to the DeviceNet network, a round cable was

factory installed between a port in the trunk line located in the top

horizontal wireway and a port in the bottom low voltage panel (see

Figure 8.1). This cable must be unplugged at both ends and removed in

order to install and connect the controller kit to the network.

Each end of the vertical flat cable assembly on the low voltage panel of

the kit has a port to which a round cable is connected. The round cables

are provided with a 5-terminal connector on their loose end. Once the

controller kit has been installed, the DeviceNet connections may be

completed. Connect the round cable at the top of the low voltage panel

to the closest port on the trunk line located in the horizontal wireway (see

Figure 8.2). Then connect the round cable at the bottom of the low

voltage panel to the port located at the top of the bottom low voltage

panel.