Re-location of termination resistors – Rockwell Automation 1500 DeviceNet MV Controllers Installation Instructions User Manual

Page 16

Advertising
background image

4-4

Linking DeviceNet Communication Cables in Medium Voltage Controllers

1500-IN057C-EN-P – June 2013

General

If any MV controller units are relocated such that the termination

resisters are no longer at the end of the trunk line, then they must be

removed and re-installed at the end of the lineup. A unit that is added to

either end of the lineup must also have the termination resister relocated

from the existing end unit to the added unit. The number of and type of

sections shown below is arbitrary and for illustration purposes only.

Drawings are not to scale.

If you have questions about re-installing termination resisters into the

trunk line of your MV controller line-up, contact Rockwell Automation

technical support.

Unit added

to right end

of lineup

Unit added

to left end

of line-up

Existing left
end section

of lineup

Existing right

end section

of lineup

Termination resistor moved to end unit when adding unit(s).

Unit added

to right end

of lineup

Unit added

to left end

of line-up

Existing left
end section

of lineup

Existing right

end section

of lineup

Termination resistor moved to end unit when adding unit(s).

Figure 4.2 – Re-location of Terminating Resistors (when additional units are added to MV Controller Line-up)