6-2

DeviceNet Power Supply

1500-IN057C-EN-P – June 2013

Figure 6.1 – LV Panel of Incomer with DeviceNet Power Supply

Network Grounding at the Power Supply

The DeviceNet cable must be grounded at only one location. The ideal

choice is at the power supply. Ground the power supply and 24 Vdc

common (black wire).

Best Grounding Practice

If the power supply comes installed in the MV controller, the black

24 Vdc common terminal is grounded to a TE ground within the MV

controller; the TE ground is connected to the cabinet ground bus. To

improve the grounding, disconnect the black 24Vdc common from

the TE ground then use #8 AWG green wire and ground the black 24

Vdc common terminal to a very stable ground external to the MV

controller line-up.

If the power supply is external, use the #8 AWG green wire and

ground the black 24 Vdc common terminal to a very stable ground.

Note:

Optional equipment
is also shown.