Typical devicenet scanner examples, Chapter – Rockwell Automation 1500 DeviceNet MV Controllers Installation Instructions User Manual

Page 17

Advertising
background image

Chapter

5

1500-IN057C-EN-P – June 2013

Typical DeviceNet Scanner Examples

The following examples illustrate typical DeviceNet networks, including

both the MV controller line-up and DeviceNet Scanner(s). The

appropriate location for terminating resistors is shown for reference.

DeviceNet

Scanner

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

121Ohms

DeviceNet

Scanner

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

LV

LV

MV

MV

121Ohms

You must attach a terminating resistor of 121 ohms, 1%, 1/4W or larger, to each end of the trunk line.
You must connect these resistors directly across the blue and white wires of the DeviceNet cable.

Figure 5.1 – DeviceNet Scanner Remote from MV Controller Line-up; one DeviceNet Network