Minimum spacing, Mounting angle, Panel guidelines – Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual

Page 19: Panel cutout dimensions

Advertising
background image

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010

19

Installation Chapter 2

Minimum Spacing

Plan for adequate space around the terminal, inside the enclosure, for ventilation
and cabling. Consider heat produced by other devices in the enclosure. The
ambient temperature around the terminal must be 0…50 °C (32…122 °F).

Mounting Angle

You can mount the terminal vertically against the panel, or tilted forward or
backwards, up to a 45° angle. For mounting angles greater than 45°, the operating
temperature is restricted to 40 °C (104 °F).

Panel Guidelines

Supporting panels must be at least 16 gauge to provide proper sealing against
water and dust and to provide proper support. The panel surface must be flat and
free of imperfections to maintain an adequate seal and NEMA Type ratings.

Panel Cutout Dimensions

Use the template shipped with your terminal to mark the cutout dimensions.

PanelView
Component

Top

Bottom

Sides

Back

C200 and C300 Keypad
C600 Touch

51 mm (2 in.)

51 mm (2 in.)

25 mm (1 in.)

13 mm (0.5 in.)

TIP

The minimum spacing requirements are sufficient for connecting cables
and inserting or removing a memory card. Plan for additional clearance if
using the USB host port on the back of the unit.

PanelView Component Terminal

Height, Approx., mm (in.) Width, Approx., mm (in.)

C600 Touch

135.0 ± 1.0 (5.31 ± 0.04)

189.0 ± 1.0 (7.44 ±0.04)