Configuration with the panelview component c600 – Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual

Page 47

Advertising
background image

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010

47

Configuration Chapter 3

Edit a Parameter

Follow these guidelines to edit a parameter:

• Press <up> or <down> to change the highlighted digit.
• Press <up> and <down> together to move the highlight cursor one place

to the left, and press <up> or <down> to set the selected digit’s value.

Continue in the same way until the correct value is entered then press <enter>
when done.

Configuration with the
PanelView Component
C600 Terminal (optional
HMI only)

The optional PanelView Component C600 terminal provides you with a more
user-friendly interface to the capacitor bank controller. Use the navigation
buttons on the bottom of each screen to navigate through the screens.

TIP

If the Capacitor Bank HMI screens are not showing up, you will need to
run the application through the PanelView Component terminal menu.
The application project name is 1413-CAP-V3.

TIP

Only solid fields are configurable; that is, the values in solid fields can be
changed.

These images show the navigation through the
PanelView Component terminal.

Clicking each button provides navigation to the
configuration and metering screens.

This screen shows current realtime Power (kW,
kVAR, and powerfactor) and displays the status of
which capacitor bank steps are currently On or OFF.

The Navication/Menu screen provides navigation
to the different screens.