Rockwell Automation Publication 1413-UM001D-EN-P - November 2010

25

Installation Chapter 2

4.

Apply 24V DC power to the terminal.

Mount the PowerMonitor
1000 Unit

The PowerMonitor 1000 unit can be mounted on a panel or a DIN rail.

Panel Mount

Follow these steps to mount the unit on a panel or any flat surface.

1.

Extend the top and bottom DIN-rail clips to the panel mount position.

2.

Insert a small screwdriver under the spring pin to move the clip, lift it, and
pull the clip forward until it extends approximately 6 mm (0.25 in.) from
the enclosure.

3.

Release the pin and lock the clip in the panel mount position.

4.

Mount the unit by using three #8 machine screws.

DIN-rail Mount

You can mount the unit on standard 35 x 7.5 mm (EN 50 022 – 35 x 7.7) DIN-
rail. To mount on a DIN-rail, leave the mounting clips retracted so the mounting
holes are hidden behind the unit.

Install on a DIN-rail

Follow these steps to mount the unit on a DIN-rail.

1.

Tilt the bottom of the unit slightly away from the rail until the notches
grab onto the top flange of the DIN-rail.

2.

Push the bottom of the enclosure forward towards the DIN-rail.

The spring-loaded clip snaps onto the bottom of the rail and holds the unit
firmly in place.

DC+

Functional
Earth Ground
to Ground Bus

DC-