Chapter 2 Installation

Connect Power

The PanelView Component terminal connects to a customer supplied 24V DC,
10 W (minimum) power source

(1)

. The table shows the power rating.

The internal, nonisolated power supply is protected against reverse polarity of the
DC+ and DC- connections.

The input power terminal block supports these wire sizes.

Follow these steps to connect power.

1.

Verify that the terminal is not connected to a power source.

2.

Secure the 24V DC power wires to the terminal block.

3.

Secure the functional earth ground wire to the functional earth ground
terminal screw on the terminal block.

Table 5 - Power Ratings

PanelView
Component

Input Voltage Range

Power Consumption, Max

C600

18…30V DC (24V DC nom)

10 W (0.42 A)

(1) We recommend an Allen-Bradley Bulletin 1606 power supply.

ATTENTION: Connecting DC+ or DC- source to the functional earth
terminal may damage the device. Miswiring the DC+ source to the DC-
input while connected to other equipment through nonisolated ports may
cause a ground loop current and damage the device.

Table 6 - Wire Specifications for Input Power Terminal Block

Wire Type

Dual-wire Gauge

(1)

(1) Two-wire maximum per terminal.

Single-wire
Gauge

Terminal Screw
Torque

Stranded or
solid

Cu 90 °C (194 °F)

0.33…1.31 mm

2

(22…16 AWG)

0.33…2.08 mm

2

(22…14 AWG)

0.45…0.56 N•m
(4…5 lb•in)

ATTENTION: Disconnect all power before installing or replacing
components. Failure to disconnect power may result in electrical shock or
damage to the terminal.