Rockwell Automation 1413-CAP-ME-PE Capacitor Bank Controller, Series C User Manual

Page 26

Advertising
background image

26

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010

Chapter 2 Installation

Remove from a DIN Rail

Follow these steps to remove the unit from a DIN-rail.

1.

Insert a small screwdriver into the exposed slot in the tab to remove the
unit from the DIN rail.

2.

Pull enclosure forward and remove from the rail.

Connect the Controller,
PanelView Component
Terminal, and the
PowerMonitor 1000 Meter

Follow these steps to connect the Capacitor Bank controller parts.

1.

Connect a source of 120/230V AC to the control power terminals on the
MicroLogix 1400 controller.

See the MicroLogix 1400 Programmable Controllers Installation
Instructions, publication

1766-IN001,

for wiring recommendations.

2.

Connect a source of 24V DC to the PanelView Component terminal.

The 24V DC power can be obtained from a 24V DC, 10 W (minimum)
power supply

(1)

that you provide.

See the PanelView Component Installation Instructions, publication

2711C-IN001

, for wiring recommendations.

3.

Connect the PowerMonitor 1000 meter to the power circuit, control
power, and earth ground.

(1) We recommend an Allen-Bradley Bulletin 1606 power supply.

IMPORTANT

Verify that the PowerMonitor 1000 meter is wired properly and
that the power metering is correct. Incorrect wiring of the PTs and
CTs will cause unpredictable capacitor bank control.