SCADA Interface

Power-circuit Parameters

The capacitor bank controller reads power-circuit parameters from the
PowerMonitor meters and makes that data available in its data table for use by
other applications such as SCADA or HMI systems.

This table lists the PowerMonitor meter data available in the controller. The
symbol x indicates the PowerMonitor meter number. Addresses related to
PowerMonitor meter no. 1 begin with F11:0, addresses related to PowerMonitor
meter no. 2 begin with F12:0.

Table 14 - Available PowerMonitor Meter Data

Address

Parameter

F1x:0

L1 Current

F1x:1

L2 Current

F1x:2

L3 Current

F1x:3

L1-L2 Voltage

F1x:4

L2-L3 Voltage

F1x:5

L3-L1 Voltage

F1x:6

Frequency

F1x:7

L1 Real Power

F1x:8

L2 Real Power

F1x:9

L3 Real Power

F1x:10

Total Real Power

F1x:11

L1 Reactive Power

F1x:12

L2 Reactive Power

F1x:13

L3 Reactive Power

F1x:14

Total Reactive Power

F1x:15

L1 Power Factor

F1x:16

L2 Power Factor

F1x:17

L3 Power Factor

F1x:18

Total Power Factor