Wiring

!

ATTENTION: Special high level
isolation is required between units when
the possibility of high ground potential
differences exist. This may occur when
separate grounds are used or when
communicating to a unit connected to a
power ground mat. Failure to do so can
lead to personal injury or death, property
damage, or economic loss.

Table A. Wiring Connections

Connector

Communication

Format

Terminal #

(Counting

from the

bottom up)

Terminal

Label

Intended Use, Pin Connection,

or Wire Color

Recommended

Cable Type

Maximum Cable

Length/Baud Rate

12

Do not connect

11

Do not connect

10

SHLD

Cable shield grounding point

2 ire shielded

RS-485

9

Minus signal data

2-wire shielded

(Belden 9841)

4000 ft/19.2kB

RS 485

8

+

Plus signal data

(Belden 9841)

4000 ft/19.2kB

7

RXD

PC Transmit, DB25, pin 2,
(DB9, pin 3)

RS-232

6

TXD

PC Receive, DB25, pin3 (DB9, pin 2)

3-wire Shielded

50 ft/19 2kB

RS-232

5

SG

PC signal return, DB25, pin 7
(DB9, pin 5)

3-wire Shielded

(Belden 9608)

50 ft/19.2kB

4

SHLD

Cable Shield

3

1

Blue Wire insulation

1770-CD

T i

i l

10,000 ft /57.6kBaud

R-I/O

2

SHLD

Cable shield ground point

1770 CD

Twinaxial

(Blue Hose)

10,000 ft /57.6kBaud

5,000 ft/115.2kBaud

2 500 ft/230 4kB d

R I/O

1

2

Clear wire insulation

(Blue Hose)

(Belden 9463)

5,000 ft/115.2kBaud

2,500 ft/230.4kBaud

Notes:

1. The communications topology for both R I/O and

RS-485 is designed to operate in a daisy-chain
topology. Use of the star or bridging method will
cause signal distortion unless impedances are
matched for each spur. Bridging is not recommended
without matching networks.

2. To prevent end reflections, each end of the daisy-

chain should be terminated in the characteristic
impedance for the cable, the baud rate, and frequency
used.

Communication

Format

Baud Rate

Terminating

Resistor

RS-485

1200–19.2k

150

1/4 W

R I/O

57.6–115.2k

150

1/4 W

R I/O

230.4k

84

1/4 W

3. Each end section of cable should have the shield

connected to the terminal labeled SHLD. This SHLD
ground provides a high frequency ground, while
limiting DC or power line frequencies from flowing
down the cable shield.

4. The RS-485 receivers in the communications card

provide a 1/4 load impedance instead of the normal
full load impedance. This therefore allows the use of
four times the number of receivers (32

 4 or 128

total) on one network.