background image

D–7

Sample Ladder Listing

Publication 1403-5.1

Rung 2:9
| Cumulative |
| Power |
| BTR |
| +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |
+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+
| |Expression | |Rack 01| |
| |N9:0 = 42 | |Group 0+–(DN) |
| +––––––––––––––––––+ |Module 0| |
| |Control block N42:0+–(ER) |
| |Data file N72:1| |
| |Length 45| |
| |Continuous N| |
| +–––––––––––––––––––––––+ |
Rung 2:10
| Device |
| Config |
| BTR |
| +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |
+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+
| |Expression | |Rack 01| |
| |N9:0 = 43 | |Group 0+–(DN) |
| +––––––––––––––––––+ |Module 0| |
| |Control block N43:0+–(ER) |
| |Data file N73:1| |
| |Length 44| |
| |Continuous N| |
| +–––––––––––––––––––––––+ |
Rung 2:11
| Comm. |
| Config |
| BTR |
| +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |
+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+
| |Expression | |Rack 01| |
| |N9:0 = 44 | |Group 0+–(DN) |
| +––––––––––––––––––+ |Module 0| |
| |Control block N44:0+–(ER) |
| |Data file N74:1| |
| |Length 30| |
| |Continuous N| |
| +–––––––––––––––––––––––+ |
Rung 2:12
| Demand |
| BTR |
| +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |
+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+
| |Expression | |Rack 01| |
| |N9:0 = 45 | |Group 0+–(DN) |
| +––––––––––––––––––+ |Module 0| |
| |Control block N45:0+–(ER) |
| |Data file N75:1| |
| |Length 42| |
| |Continuous N| |
| +–––––––––––––––––––––––+ |
Rung 2:13
| Even |
| Harmonic |
| Distortion |
| BTR |
| +CMP–––––––––––––––+ +BTR––––––––––––––––––––+ |
+–+COMPARE +––––––––––––––––––––––––––+BLOCK TRANSFER READ +–(EN)–+
| |Expression | |Rack 01| |
| |N9:0 = 46 | |Group 0+–(DN) |
| +––––––––––––––––––+ |Module 0| |
| |Control block N46:0+–(ER) |
| |Data file N76:1| |
| |Length 60| |
| |Continuous N| |
| +–––––––––––––––––––––––+ |

Rung 2:9

Cumulative power BTR.

Rung 2:10

Device configuration BTR.

Rung 2:11

Communication configuration
BTR.

Rung 2:12

Demand BTR.

Rung 2:13

Even harmonic distortion BTR.

Advertising