Sample Ladder Listing

Publication 1403-5.1

The SLC-500 R I/O version requires that all read and
write tables be 64 words in length. This is a necessary
requirement stemming from the use of the block transfer
subroutines.

A four word length control file needs to be initialized for
each individual block transfer subroutine. The
initialization values for each word are discussed in the
Data Files Used section.

SLC-500 RS-232 Operation

Use of an SLC-500 MSG instruction in place of the BTW
and BTR instructions is the only difference between the
PLC-5 R I/O and the SLC-500 RS-232 versions of the
Powermonitor II sample ladder.

PLC-5 R I/O Data Files Used

Data File

Address

Data File

Size

Description

B3

20

b3/0 Configuration mode enable

b3/2 Run mode enable

b3/1 Setpoint mode enable

b3/300 One-shot bit

b3/301 One-shot bit

b3/302 One-shot bit

b3/303 One-shot bit

b3/304 One-shot bit

N9

1

N9:0 Sequencer output

N10

variable

N10:0 Sequencer input

Data File

Address

Data File

Size

Description

N11

3

N11:0 Sequencer input data for
configuration mode

N12

3

N12:0 Sequencer input data for
setpoint mode

N13

variable

N13:0 Sequencer input data for
run mode

N20

2

N20:0 Number of setpoints

N20:1 Temporary storage for
setpoint address

N22

21

Setpoint #1 location

N23

21

Setpoint #2 location

N39

21

Setpoint #20 location

R6:0

Sequencer control

BTR Data Table Locations

(control / data)

N40 / N70

54

Voltage/current data

N41 / N71

63

Real-time power

N42 / N72

46

Cumulative power

N43 / N73

45

Device configuration

N44 / N74

31

Communication configuration

N45 / N75

43

Demand

N46 / N76

61

Even harmonic distortion

N47 / N77

62

Odd harmonic distortion

N48 / N78

59

Even harmonic magnitude

N49 / N79

58

Odd harmonic magnitude

N50 / N80

57

Even harmonic phase

N51 / N81

56

Odd harmonic phase

N52 / N82

40

Diagnostic

N53 / N83

39

Relay/setpoint

BTW Data Table Locations

(control / data)

N54 / N84

23

Command

N55 / N85

45

Device configuration

N56 / N86

21

Setpoint

Sequencer input file N10 contains a list of the block
transfers required to complete the active mode. The
contents of N10 are copied from N11 for Configuration
mode, N12 for Setpoint mode and N13 for Run mode
during each mode’s initialization.