D–15

Sample Ladder Listing

Publication 1403-5.1

Rung 2:17
Perform appropriate block transfer read.
| +EQU–––––––––––––––+ +JSR–––––––––––––––+ |
|–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|
| |Source A N9:0| |SBR file number 3| |
| | 40| +––––––––––––––––––+ |
| |Source B 50| |
| | | |
| +––––––––––––––––––+ |
Rung 2:18
Perform appropriate block transfer read.
| +EQU–––––––––––––––+ +JSR–––––––––––––––+ |
|–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|
| |Source A N9:0| |SBR file number 3| |
| | 40| +––––––––––––––––––+ |
| |Source B 51| |
| | | |
| +––––––––––––––––––+ |
Rung 2:19
Perform appropriate block transfer read.
| +EQU–––––––––––––––+ +JSR–––––––––––––––+ |
|–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|
| |Source A N9:0| |SBR file number 3| |
| | 40| +––––––––––––––––––+ |
| |Source B 52| |
| | | |
| +––––––––––––––––––+ |
Rung 2:20
Perform appropriate block transfer read.
| +EQU–––––––––––––––+ +JSR–––––––––––––––+ |
|–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|
| |Source A N9:0| |SBR file number 3| |
| | 40| +––––––––––––––––––+ |
| |Source B 53| |
| | | |
| +––––––––––––––––––+ |
Rung 2:21
Perform appropriate block transfer write.
| +EQU–––––––––––––––+ +JSR–––––––––––––––+ |
|–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|
| |Source A N9:0| |SBR file number 4| |
| | 40| +––––––––––––––––––+ |
| |Source B 54| |
| | | |
| +––––––––––––––––––+ |
Rung 2:22
Perform appropriate block transfer write.
| +EQU–––––––––––––––+ +JSR–––––––––––––––+ |
|–+EQUAL +––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–|
| |Source A N9:0| |SBR file number 4| |
| | 40| +––––––––––––––––––+ |
| |Source B 55| |
| | | |
| +––––––––––––––––––+ |
Rung 2:23
Begin run mode once all setpoint block transfers are complete.
| One Shot 4 Status – Setpoint Setpoint |
| Bad Table Counter Mode |
| Check Done Bit |
| +EQU–––––––––––––––+ B3 +EQU–––––––––––––––+ C5:0 B3 |
|–+EQUAL +–––[OSR]––––+EQUAL +––––] [–––+––––(U)–––––+–|
| |Source A N9:0| 303 |Source A N82:36| DN | 1 | |
| | 40| | 0| | | |
| |Source B 56| |Source B 0| | | |
| | | | | | | |
| +––––––––––––––––––+ +––––––––––––––––––+ | | |
| | Run | |
| | Mode | |
| | B3 | |
| +––––(L)–––––+ |
| 2 |

Rung 2:17

Even harmonic phase BTR.

Rung 2:18

Odd harmonic phase BTR.

Rung 2:19

Diagnostic BTR.

Rung 2:22

Configuration BTW.

Rung 2:20

Relay/setpoint BTR.

Rung 2:21

Command BTW.

Rung 2:23

If the setpoint counter done bit
is set, the last setpoint BTW has
occurred and was followed by a
diagnostic BTR. If the
diagnostic table indicates a
successful setpoint BTW,
setpoint mode is done. The
setpoint mode bit is unlatched,
and the run mode bit is latched.