Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

13

Bulletin 1609 UPS

Mount the UPS

The 1609-B UPS products are designed to mount to a heavy duty DIN-rail
(see Figure 3 below). The 1609-B UPS products are also designed with an
optional bracket assembly (Cat 1609-BRK) that allows it to mount to either
the panel or floor (see Figure 4 below).

Figure 3 - Standard DIN-Rail Mount

Figure 4 - Optional Panel or Floor Mount

Hardwire UPS

Wiring of the UPS should be performed by a qualified electrician using the
appropriate wire gauges.

Selection of Cables

Table 3 - AC Main Input / Output Wiring for UPS

Item

Specification

Wire Size

14 AWG

Minimum Temperature

75 °C

Wire Conductor Material

Copper only

Tightening Torque for Terminals

4.4 lb - in.

WARNING: To reduce the risk of fire, connect only to a circuit with 20 amperes
maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.

A disconnect switch shall be provided by others for AC output circuit.
To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent
protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.