Bul. 1609-b specifications – Rockwell Automation 1609-B_D UPS Product User Manual User Manual

Page 28

Advertising
background image

28

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

Bulletin 1609 UPS

Bul. 1609-B Specifications

1609-B600N

1609-B1000N

Input

V nom.

120V

120V

Capacity

600 VA (360 W)

1000 VA (600 W)

Voltage Range, default

96...138V

Voltage Range, widest online

96...138V

Current nom.

5.4 A

8.9 A

Capacity Frequency

50/60 Hz ± 3 Hz

50/60 Hz ± 3 Hz

PFC

None None

Output

V nom.

120V

Capacity

600 VA (360 W)

1000 VA (600 W)

Online

Output Voltage Range, default

96...138V

Output Voltage Range, widest online

96...138V

Transfer Point Accuracy

± 3%

On Battery

V nom

120V (step wave)

Frequency

50/60 Hz ± 1 Hz

THD

47.5% (step wave)

47.6% (step wave)

Short Circuit Protection

Crest Factor

2.5:1

Efficiency

On Battery (Typical with resistive load)

80% Typical with resistive load

Online - Typical with resistive load excluding AVR mode) 94% Typical with resistive load

Protection

Surge

380 Joules (Total performance rated with 10*1000 μ s pulse)

Overload (Shutdown after 10 s)

> 110...130% - shutdown after 5 sec

Overload (Shutdown immediately)

130% shutdown immediately

Output Short: Online

Premises branch circuit over-current protection

Output Short: Battery

Shutdown

Thermal Protection

UPS inside temperature ≥ 70 °C

Regulatory

Safety

UL1778, CSA C22.2 No. 107.3-05, EN/IEC62040-1

EMC

FCC & CE (Class A)

Markings

UL, cULus, FCC, CE, C-Tick

Battery Pack

Run Time

≥5 min (at 25 °C, full load = 360W, PF = 0.6...0.75)

≥2 min (at 25 °C, full load = 600W, PF = 0.6...0.75)

Type

Sealed Lead Acid Battery

12V/5Ah (for 0...40 °C: B.B. BP5...12)

12V/5.5 Ah (for 0...50 °C: B.B. HRL5.5...12)

Voltage

24V

Charger

Current limited, constant voltage float charger

Recharger Time

Less than 12 hrs to 90% capacity after discharge with full load

Lifetime

2...3 years at 25 °C ambient temperature

Environment

Temperature

Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Non-operating/Storage -15...+45 °C (+5...+113 °F)

Altitude

Operating 0...6600 feet (0... 2000 meters)

Humidity

Operating/Storage 5...95% RH (Non-condensing)

Heat Output

On Line, Full load: 107 BTU/hr
On Line, Full load, Charging: 160 BTU per hour
On Battery: Full Load: 1228 BTU per hour

On Line, Full load: 178 BTU/hr
On Line, Full load, Charging: 231 BTU per hour
On Battery: Full Load: 2047 BTU per hour

Audible Noise

< 45 dBA @ Front Side 1 Meter

Mechanical

Approximate Dimensions L*W*H In. (mm)

6.1 x 11 x 7.09 (155 x 300 x 180)

Approximate Weight lbs (kg)

14.5 (6.6)

14.7 (6.7)

Advertising