Troubleshooting – Rockwell Automation 1609-B_D UPS Product User Manual User Manual

Page 22

Advertising
background image

22

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

Bulletin 1609 UPS

Troubleshooting

Button

Function

Explanation

UPS Output Enable

Press and hold the button until one beep is heard, then release
immediately

UPS Output Disable

Press and hold the button until three beeps are heard, then release
immediately

Self-Test

Press and hold the button until two beeps are heard, then release
immediately (The UPS must operate for at least 4 hours before executing
this function)

Problem

Possible Cause

Solution

No LED illuminates /
No alarm

UPS output is disabled or input utility
power is not present

Have qualified electrician trouble shoot the input utility
power system and make the necessary corrections.

No UPS output

The UPS has not been enabled

Manually Enable - Make sure the Remote Function
selector switch is in the Disable position, then press and
hold the UPS Power button until one beep is heard and
release immediately.
Remotely Enable - Make sure the Remote Function
selector switch is in the Enable position and verify that
there is an adequate connection to the remote on/off dry
I/O connection (terminals 7 & 8)

UPS Operates on battery
although input utility
voltage exists

The system may experience high, low
or distorted input utility voltage

Reduce the UPS sensitivity by using the 1609 UPS
Management software.
If the problem persists, move or connect the UPS with a
known good quality utility power source.

Input line utility power
circuit breaker trip

The system may have experienced an
overload

Verify that the circuit breaker is sized properly.
Verify the load connected to the output of the UPS. Ensure
that the load does not exceed the output rating of the UPS.

FAULT LED illuminates

An internal fault has been detected

Refer to the UPS LED Fault Indicators below to identify the
specific fault that occurred and possible resolution.

ONLINE LED illuminates, but
no UPS output is available

The UPS output connection may not
be connected properly

Disable the UPS output and have qualified electrician
troubleshoot the output connection system and make the
necessary corrections.

The battery did not provide
expected runtime

The batteries might be weak or the
lifespan is due

Charge the batteries for 8 hours and retest the runtime.
If the runtime is still less than expected after charging,
replace the batteries even if the Replace Battery LED doesn’t
illuminate.

No communication
between the
UPS and your PC

Wrong cable

Verify cable used.

The connection cable is not firmly
connected

Reconnect the communication cable firmly.

PC Communication Port may have
been used by another process or is
defective

Check if there is other software or service accessing the
Communication Port on your PC, or connect it to a different
communication port.

There is interference on the
connection cable

Lay the cable differently or away from other cables and
reconnect the cable.