Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

9

Bulletin 1609 UPS

Hardwire UPS

Wiring of the UPS should be performed by a qualified electrician using the
appropriate wire gauges.

Selection of Cables

Table 1 - AC Main Input/Output Wiring for UPS:

Table 2 - DC Input / Output Wiring for External Battery Cabinet:

Item Specification

Wire Size

14 AWG

Minimum temperature

75 °C

Wire conductor material

Copper only

Tightening torque for terminals

4.4 lb-in.

Item Specification

Wire Size

10 AWG

Minimum temperature

75 °C

Wire conductor material

Copper only

Tightening torque for terminals

12 lb-in.

WARNING: To reduce the risk of fire, connect only to a circuit with 20 amperes
maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.

A disconnect switch shall be provided by others for AC output circuit.
To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent
protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.