Ups led fault indicators – Rockwell Automation 1609-B_D UPS Product User Manual User Manual

Page 23

Advertising
background image

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

23

Bulletin 1609 UPS

UPS LED Fault Indicators

General Clear Fault Procedure

Press and hold the button until three beeps are heard then release immediately
to turn the UPS off then press and hold the button again until one beep is
heard then release to enable the output.

No.

Fault

Description

Solution

1

Output Short Circuit

The UPS has detected a
short circuit on the Output
of the UPS and disabled its
output.

Have a qualified electrician troubleshoot the load connected to the output to the UPS and remove the
short circuit if present.

2

Output Overload

The UPS has detected an
overload and disabled its
output.

To clear fault, follow the General Clear Fault Procedure described above. If the problem persists, contact
Technical Support.
Verify the load connected to the output of the UPS. Ensure that the load does not exceed the output
rating of the UPS. If the load exceeds the rating of the UPS please remove excess load or select the
appropriate size UPS. If the problem persists, contact Technical Support.
To clear fault, follow the General Clear Fault Procedure described above.

3

Over Temperature from the
Heatsink

The UPS has detected an
over temperature of the
heatsink and disabled its
output.

Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C
(1609-SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the
system. This issue may be corrected by improving the room ambient temperature (add ventilation or
provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.

4

Over Ambient Temperature

The UPS has detected an
over ambient temperature
and disabled its output.

Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C
(1609SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the
system. This issue may be corrected by improving the room ambient temperature (add ventilation or
provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.

5

Over Voltage from The DC/DC
Converter of Inverter

The UPS has detected an
over voltage of the DC/DC
Converter and disabled its
output.

Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear the fault, follow the General Clear Fault Procedure described above.
If the fault is still present after attempting to clear fault, contact Technical Support.

6

Over Voltage from The Inverter

The UPS has detected high
voltage on the inverter
and disabled its output.

Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear fault, follow the General Clear Fault Procedure described above.
If the fault is still present after attempting to clear fault, contact Technical Support.

7

Under Voltage from The Inverter

The UPS has detected low
voltage on the inverter
and disabled its output.

Have a qualified electrician verify that the quality of utility voltage is within specification.
To clear fault, follow the General Clear Fault Procedure described above.
If the fault is still present after attempting to clear fault, contact Technical Support.