Bul. 1609-d specifications – Rockwell Automation 1609-B_D UPS Product User Manual User Manual

Page 27

Advertising
background image

Rockwell Automation Publication 1609-UM009A-EN-P - January 2013

27

Bulletin 1609 UPS

Bul. 1609-D Specifications

1609-D600N

1609-D1000N

1609-D1500N

Input

V nom.

120V

120V

120V

Capacity

600 VA (390 W)

1000 VA (650 W)

1500 VA (980 W)

Voltage Range, default

90...145V

90...145V

90...145V

Voltage Range, widest online

90...145V

90...145V

90...145V

Current nom.

5.5 A

8.8 A

13 A

Capacity Frequency

50/60 Hz ± 3 Hz

50/60 Hz ± 3 Hz

50/60 Hz ± 3 Hz

PFC

None None

None

Output

V nom.

120V

Capacity

600 VA (390 W)

1000 VA (650 W)

1500 VA (980 W)

Online

Output Voltage Range, default

108...132 V

Output Voltage Range, widest online

108...132 V

Transfer Point Accuracy

± 3 %

On Battery

V nom

120V (sine wave)

Frequency

50/60 Hz ± 0.5Hz

THD

≤ 10% Full Linear Load

Short Circuit Protection

Crest Factor

2.2:1

Efficiency

On Battery (Typical with resistive load)

75%

Online - Typical with resistive load excluding AVR mode) 86%

94%

95%

Protection

Surge

380 Joules

Overload (Shutdown after 10 s)

> 110...130%

Overload (Shutdown immediately)

130%

Output Short Online/Battery

Premises branch circuit over-current protection/Shutdown

Thermal Protection

UPS inside temperature ≥ 60 ºC

Regulatory

Safety

UL1778, CSA C22.2 No. 107.3, EN/IEC62040-1

EMC

FCC & CE (EN 62040-2)

Markings

UL, cULus, FCC, CE, C-Tick

Battery Pack

Run Time

≥5 min (at 25 °C, full R load)

≥3.5 min (25 °C, full R load)

≥2.5 min (at 25 °C, full R load)

Type

Sealed Lead Acid Battery 12V/5Ah (for 0...40 °C B.B. BP5-12) 12V/5.5Ah (for 0...50 °CB.B. HRL5.5-12)

Voltage

36V

Charger

Current limited, constant voltage float charger

Recharger Time

Less than 8 hr to 90% capacity after discharge with full load

Lifetime

2...3 years at 25 °C ambient temperature

Environment

Temperature

Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Non-operating/Storage -15...+45 °C (+5...+113 °F)

Altitude

Operating 0...6600 feet (0... 2000 meters)

Humidity

Operating/Storage 5...95% RH (Non-condensing)

Heat Output

On Line, Full load: 217 BTU/hr
On Line, Full load, Charging:
296 BTU per hour
On Battery: Full Load: 1331 BTU
per hour

On Line, Full load: 142BTU/hr
On Line, Full load, Charging:
221 BTU per hour
On Battery: Full Load: 2218BTU
per hour

On Line, Full load: 176BTU/hr
On Line, Full load, Charging:
256BTU per hour
On Battery: Full Load: 3344BTU
per hour

Audible Noise

< 50 dBA @ Front Side 1 Meter

Mechanical

Approximate Dimensions L*W*H In. (mm)

8.66 x 16.14 x 10.24 (220 x 410 x 260)

Approximate Weight lbs (kg)

29.7 (13.5)

30.1 (13.7)

31 (14.1)