Table 3 - system status description, Voltage sag events, Voltage sag log – Rockwell Automation 1608P ProDySC User Manual, 100/110 A User Manual

Page 22: Figure 17 - voltage sag log, Table 4 - voltage sag log description, Voltage sag

Advertising
background image

22

Rockwell Automation Publication 1608P-UM002A-EN-P - July 2013

Chapter 5

Display Screen

Table 3 - System Status Description

Voltage Sag Events

A voltage sag is defined as the period when input RMS voltage drops to less than
88.5% of the rated DySC voltage. Details of each voltage sag and corresponding
ProDySC protection are captured and saved to the voltage sag log.

Voltage Sag Log

The "Voltage Sag Log" screen (See

Figure 17

) displays a list of the last 61 voltage

sags. Reach this screen by pressing "VOLTAGE SAGS" button on the "HOME"
screen.

Figure 17 - Voltage Sag Log

Table 4 - Voltage Sag Log Description

Description

Function

System Status

Overall system status including current operational status, availability to correct sags, and internal cabinet temperature

Phase Status

Voltage, current, frequency, and static switch temperature are displayed for all phases. The percentage displayed following the voltage and
current is the percent of nominal value for the ProDySC. Nominal values are listed on the “View Model Information” screen.

Waveforms

A sample of a 4 cycle waveform that includes real-time line voltage, load voltage, or load current can be selected for display

Description

Function

#

Unique ID within the list (0-60) to identify the voltage sag

Time

Start time and date of the voltage sag

Check Mark

Denotes the ProDySC protected the voltage sag

RMS %

Worst-case RMS voltage (percent of nominal) across all phases

Duration

Duration of the voltage sag

Note: Use the up/down arrows to navigate through the list. Press the “SELECT” button to view additional details about
the voltage sag

Advertising