Voltage Sag Detail

Voltage Sag Detail" screen (See

Figure 18

) displays all information related to the

selected event. Details for the most recent sag event can also be accessed by
pressing anywhere in the Last Voltage Sag area of the HOME screen.

The worst-case RMS voltage recorded during the event is displayed in the upper
window along with the corresponding voltage percentage and the event duration.
Table 7 describes the remaining screen content.

Figure 18 - Voltage Sag Detail

Table 5 - Voltage Sag Detail Description

Description Function

Sag Summary

ID: Unique ID within the list (0-60) to identify the voltage sag
Time: Start time of the voltage sag
RMS: Worst-case RMS voltage (L-N) and percent of rated voltage across all phases
Duration: Duration of the voltage sag
Frequency: Frequency of the line prior to the start of the voltage sag
Temperature: Internal temperature of the PRODySC prior to the start of the voltage sag

Sag Magnitude

Line Voltage: Line RMS voltage and percent of rated (L-N). Voltages <= 80% of nominal are
displayed in red.
Load Voltage: Load RMS voltage and percent of nominal (L-N).

Correction Result

The "Correction Result" is displayed in a box in the upper-right-hand corner of the "Event
Summary" section. The "Correction Result" conveys how the PRODySC performed correcting
the voltage sag. The possible values are:

Protected: The output RMS voltage on all phases is ?85 percent of nominal and the PRODySC
correction was active for the duration of the voltage sag (will be displayed in green).
Run Error: An unexpected system event occurred during the sag (will be displayed in orange)
Run Inhibited: The PRODySC system was inhibited when the sag occurred (will be displayed
in orange).

Note: The "Voltage Sag Detail" for the most recent event can also be accessed by pressing the "Last Voltage Sag" area of the "HOME"