Chapter 1, Introduction, Safety considerations – Rockwell Automation 1608P ProDySC User Manual, 100/110 A User Manual

Page 5: Ch 1 - introduction, Munications, Intenance, Ifications and dimensions, Chapter

Advertising
background image

Rockwell Automation Publication 1608P-UM002A-EN-P - July 2013

5

Chapter

1

Introduction

The Allen-Bradley Bulletin 1608P ProDySC Dynamic Sag Corrector is
engineered to provide years of trouble-free voltage sag (dip) protection. The
patented DySC technology does not use batteries, requires only routine
maintenance, includes three-stage transient voltage surge suppression, and has
unparalleled energy efficiency. Most electronic devices found in industry today
are susceptible to power disturbances. A momentary sag in line voltage can reset
or damage sensitive production equipment. The ProDySC provides
instantaneous dynamic sag correction to help your equipment ride through these
common events. The ProDySC connects normal utility power directly to the
load until a voltage sag occurs. During a sag, the ProDySC inverter is activated-
adding missing voltage to keep the load voltage within the normal range. When
utility power returns to normal, the inverter is deactivated and the ProDySC is
quickly ready to correct the next sag.

The ProDySC reports these voltage sag events through its integrated touch
screen display and provides system status, voltage sag notification and history,
runtime statistics and system history in a simple and intuitive touch-based user
interface.

Safety Considerations

The ProDySC is designed to operate in industrial applications. Follow these
guidelines to ensure that the safety and installation of the ProDySC are handled
with appropriate care.

SHOCK HAZARD: The ProDySC has high voltage remaining up to 5 minutes
after disconnection from the AC line. Touching exposed or disconnected
terminals, cables or parts of the ProDySC can lead to serious injuries or even
death. Wait for a minimum of 5 minutes before performing any service or
testing on the DySC after power is removed.
Keep the cabinet doors closed to ensure proper cooling airflow and to protect
personnel from dangerous voltages inside the ProDySC.

ATTENTION: - To reduce the risk of fire or electric shock, install this ProDySC in
a temperature and humidity controlled, indoor environment, free of conductive
contaminants.

Avoid installing the ProDySC directly near heat-emitting equipment such as ovens, heaters, or

furnaces.

Ambient temperature must not exceed 40°C (104°F).
Do not operate near water or excessive humidity (95% max).
When punching or drilling holes for conduit fittings, take care to avoid dropping metallic particles

inside the enclosure as this can result in electrical damage.

The system is not intended for outdoor use.
The operating environment should be maintained within the parameters stated in this manual.
Only authorized service personnel should perform service on the ProDySC.
Ensure all power is disconnected before performing installation or service.