Rockwell Automation Publication 1608P-UM002A-EN-P - July 2013

9

Installation

Chapter 2

NOTICE: The 1608P bypass switch contacts are designed to make-before-break and will not
disrupt power to the load during any mode transitions. The switch has lockout/tagout (LOTO)
provisions.

Circuit Breaker
Recommendations

Branch circuit protection upstream of the ProDySC is required. Recommended
circuit breakers and maximum allowed circuit breaker ratings are listed in

Table 1

. Branch circuit protection rated less than the ProDySC current rating

may result in nuisance tripping.

Table 1 - Recommended Branch Circuit Protection

Electrical Terminations

The ProDySC must be installed by a qualified electrician. The ProDySC input
(line) and output (load) terminals are located behind the top door, as shown in

Figure 3

. Terminal details are shown in

Figure 7 on page 13

.

Figure 3 - Input/Output Terminal Location

ProDySC Rating

Max. MCCB Rating

100 A

125 A

110 A

150 A

INPUT/OUTPUT

NEUTRAL

BUS
GROUND

BUS