Table 1: link list – Rockwell Automation 1395 Reel Tension Paster Adapter User Manual

Page 24

Advertising
background image

Publication 1395-RTP-5.1 - September 1997

3-4

Start-Up Instructions

Connect hand held programming terminal to Drive at DHT
Connector, located to the left of TB3 at the bottom of the Drive. Upon
power-up, communications are initialized as indicated by the letter I
in Drive graphically displaying a moving pendulum.

Check LEDs on Digital Reference Adapter Board for +12V, -12V,
+5V, and +24V Status. (See Troubleshooting section for further
explanation.)

Verify links and parameters match the tables provided using the
Programmable Terminal. To access links, enter “Drive Set Up” mode,
select “Read Edit”, and view the next link each time the “ENTER”
key is depressed. If necessary, parameters and links can be entered
with the DHT or the Intelligent Terminal System, (ITS), if available
or Drive Tools software.

The following Parameter list is a quick reference table showing the
set-up parameters and values associated with an RTP start-up. (The
motor data is for G.E. and Baldor Motors, refer to proper – 18
drawings for other motors). Refer to Bulletin 1395 Drive Installation
& Maintenance Manual or associated schematics for complete
Parameter list and descriptions.

Table 1: Link List

Parameter Links

Sink

Source

450

TO

100

151

TO

400

152

TO

200

153

TO

404

154

TO

403

161

TO

407

163

TO

405

164

TO

408

165

TO

410

166

TO

411

250

TO

100