Chapter 2

Installation

Electrical Terminations and
Ratings

Input connections are marked L1, L2, and L3 for the source connections. Output
connections are marked X1, X2, and X3 for the load connections (See

Figure 5

).

In 4-wire models only, connect both input and output N conductors to the
NEUTRAL bus bar. Do not connect to the NEUTRAL bus bar in 3-wire
models. Replace all shields and covers when wiring is completed. The doors must
be closed and latched securely.

Figure 5 - Electrical Terminations

Input/Output mechanical lugs accept AWG 6 to 350 kcmil [16 to 150 mm

2

] conductors. Tighten lugs to

275 lb-in [31 N-m]. Lugs require 5/16” hex key tool for installation.

Input/Output mechanical lugs may be removed and replaced with pressure (crimp) lugs. Two 1/2” holes (1.75”

spacing) are provided.

NEUTRAL Bus and Ground Bus are provided with 3/8”-16 threaded studs (9.525mm diameter). Tighten nuts to 25 lb-ft

(300 lb-in) [33.9 N-m].

WARNING: The HC-DySC must be safety-grounded according to the National
Electrical Code. In addition, all local, state, and federal regulations applicable to
the installation of electrical systems and accident prevention regulations must
be strictly observed

Neutral Bus

Ground Bus

AC Input

Connections

AC Output

Connections

SHOWN WITH

DOOR OPEN