Voltage sag events, Voltage sag log – Rockwell Automation 1608P-200A480V... HC-DySC User Manual User Manual

Page 25

Advertising
background image

Rockwell Automation Publication 1608P-UM005A-EN-P - November 2014

25

Display Screen

Chapter 5

Voltage Sag Events

A voltage sag is defined as the period when input RMS voltage drops to less than
88.5% of the rated DySC voltage. Details of each voltage sag and corresponding
HC-DySC protection are captured and saved to the voltage sag log.

Voltage Sag Log

The “Voltage Sag Log” screen (See

Figure 19

) displays a list of the last 61 voltage

sags. Reach this screen by pressing “VOLTAGE SAGS” button on the “HOME”
screen.

Figure 19 - Voltage Sag Log

Table 5 - Voltage Sag Log Description

Description

Function

#

Unique ID within the list (0-60) to identify the voltage sag

Time

Start time and date of the voltage sag

Check Mark

Denotes the HC-DySC protected the voltage sag

RMS%

Worst-case RMS voltage (percent of nominal) across all phases

Duration

Duration of the voltage sag

Note: Use the up/down arrows to navigate through the list. Press the “SELECT” button to view additional details about
the voltage sag

Advertising